SE 5121

LIFE SAFETY VOICE ALARM SYSTEM

The Slave unit SE5121 is a high-quality modular voice alarm system specially designed to simplify the provision of a fully BS 5839 part 8 and EN 60849 compliant voice alarm system.

In one compact wall-mountable enclosure.

Applications
  • • Halls
  • • Schools
  • • Shopping centres
Part Number
  • • 17170086
Features
  • Integrated Voice Alarm modular system for emergency announcements
  • Equipped with a dual amplification circuit 2 x 60W that can drive 2 lines of speakers at 100V constant voltage
  • The system incorporates a digital reader for messages that can be activated from the fire alarm control unit
  • The preamplification circuit includes dedicated inputs for emergency microphones (BM 5001WM), preamplified announcement microphones, and background music source
  • The system operates with the mains voltage, which it also uses for recharging the batteries that automatically power it in the event of a black-out
  • The system is supplied with hermetically sealed batteries that are situated inside the enclosure itself
  • End-line sensors to be installed in parallel with the last speaker of each line to verify the continuity of the line
  • Slave amplifiers are typically used to extend loudspeaker coverage in areas such as large warehouses.
  • They also allow greater fl exibility to manage paging and background music as they have their own paging and background music inputs
AUDIO SPECIFICATIONS
  • Power output: 2 x 60 W Watt rms
  • Frequency Response: 152 ÷ 12.000 Hz
  • FRONTAL PANEL CONTROLS
  • Level Meters: Fault LED indicators
  • Bottons: PTT button, Silence Internal Sounder button, Reset button, Calibrate button
  • Connections and Wires: Twisted pairs. The wire section shall be chosen according to the connected power
  • INPUT SECTION
  • Input connector: Euroblock
  • Input sensitivity: -10.6 ÷ + 9.3 dBu
  • Number audio Input: 1
  • OUTPUT SECTION
  • Output connector: Euroblock
  • Output Loudspeaker constant voltagge: 100 V
  • POWER REQUIREMENT
  • Operating voltage: 240 Vac , 50-60 Hz
  • Max-current: 7 A
  • Power (consumption): Max 500 mA @ 24 Vdc
  • Operating temperature range: 0 ÷ +50 °C
  • Operating humidity: 20 ÷ 90 % RH non-condensing
  • Battery fuse: 5 A F 20 mm
  • Fuse model: 240 V 1 A HRC ceramic 20 mm
  • PHISICAL SPECIFICATION
  • Height: 445 / 17.51 mm/inch
  • Width: 445 / 17.51 mm/inch
  • Depth: 115 / 4.52 mm/inch
  • Net Weight: 8 / 17.63 Kg/Lbs
  • SHIPPING INFORMATION
  • Package height: 565 / 22.24 mm/inch
  • Package width: 565 / 22.24 mm/inch
  • Package depth: 195 / 7.67 mm/inch